Experimental studies on impedance based fault location for long transmission lines

查看全文 作  者:Saeed [1]Roostaee;Mini [1]S.Thomas;Shabana [1]Mehfuz 高影响力作者 机构地区:[1]Department of Electrical Engineering,Faculty of Engineering and Technology,Jamia Millia Islamia,New Delhi,India高影响力机构 出  处:《Protection and Control of Modern Power Systems》索引2017年第2卷第1期,共9页高影响力期刊 摘  要:In long transmission lines,the charging current caused by the shunt capacitance decreases the accuracy in impedance based fault location.To improve the accuracy of fault location,this paper presents a novel scheme,where two Digital Fault Recorders(DFRs)are installed in a line.They can send the transient data of the faults to the both ends of a line.To estimate the distance of a fault,impedance based fault location methods are applied with transient fault data of both ends protection relays and both DFRs installed in a line.To evaluate the proposed scheme,a laboratory setup has been developed.In the lab,several faults have been simulated and associated voltages and currents are injected to a relay IED to compare experimental results. 关 键 词:Transmission line fault location Impedance based fault location